Extinguishing agent unit (Löschmitteleinheit, LE)
Also: Löschmitteleinheit, LE, Fire extinguisher units
Definition
The extinguishing agent unit (LE) is a unit of calculation in ASR A2.2 that makes the extinguishing capacity of fire extinguishers comparable. Floor area and fire risk determine how many extinguishing agent units, and therefore how many extinguishers, an area needs.
Each fire extinguisher is assigned a number of extinguishing agent units based on its extinguishing capacity. For the basic equipment, ASR A2.2 provides a table: an area of 50 m² needs 6 LE, 100 m² 9 LE, 200 m² 12 LE, with further increasing values for larger areas. Extinguishers must be suitable for the fire classes present and reachable from any point within a walking distance of no more than 20 metres.
Where the fire risk is increased, additional measures are required, such as more extinguishers, suitable extinguishing agents or fixed systems. Under certain conditions, wall hydrants may be counted. Fire extinguishers must generally be inspected by a competent person every two years.
Legal basis
- ASR A2.2 “Measures against fires”
Learn more