Explosion protection document in Germany: contents, zoning and inspections
Wherever flammable gases, vapours, mists or dusts can form an explosive atmosphere, an explosion protection document must exist before work starts in Germany. What it must contain, how zones are defined and which inspections apply.
Last updated on 8 min readAMS Go editorial team
Key points at a glance
- If hazardous explosive mixtures can occur during work, the employer must set out the explosion hazards separately in the risk assessment – in the explosion protection document under Section 6 (9) of the German Hazardous Substances Ordinance, which must exist before work first starts.
- Protective measures follow a fixed order of priority: avoid hazardous explosive mixtures, then avoid ignition sources, then limit the effects of an explosion (Section 12 (2) GefStoffV).
- Hazardous areas are classified by how often and how long an explosive atmosphere is present into zones 0, 1 and 2 (gases, vapours, mists) or 20, 21 and 22 (dusts); this determines the permitted equipment category 1, 2 or 3 (Annex I Nos. 1.7 and 1.8 GefStoffV).
- Installations in hazardous areas must be inspected for explosion safety before first commissioning and at least every six years, and ventilation systems, gas detection and inerting systems every year (Annex 2 Section 3 BetrSichV).
What is an explosion protection document?
The explosion protection document (Explosionsschutzdokument) is the part of the risk assessment (Gefährdungsbeurteilung) in which the employer sets out the hazards from hazardous explosive mixtures separately – with the assessment, the explosion protection concept, zoning, protective measures and inspections. The legal basis is Section 6 (9) of the Hazardous Substances Ordinance (Gefahrstoffverordnung, GefStoffV). Because it is part of the documentation under Section 6 (8), it must exist before work first starts – regardless of the number of employees.
Typical areas are paint shops, solvent stores and filling stations, woodworking with dust extraction, and mills, silos and mixing plants for flour, sugar or plastic powders. According to TRGS 721, an explosion with dangerous effects is possible when four conditions coincide:
- flammable substances, finely dispersed as gas, vapour, mist or airborne dust
- a concentration in air within the explosion limits
- a dangerous quantity
- an effective ignition source
When is an explosion protection document required?
Whether you need an explosion protection document follows from the assessment of fire and explosion hazards under Section 6 (4) GefStoffV. TRGS 720 sets out the order of the assessment:
- 1
Flammable substances present?
Check whether flammable gases, liquids or dusts are present or can be formed – including during start-up and shutdown, cleaning or faults. If not, record this in the risk assessment.
- 2
Explosive atmosphere possible?
Dispersion and concentration are decisive: for liquids, for example, when they are sprayed or their flash point is not sufficiently above the processing temperature; for dusts, when they are stirred up.
- 3
Substitution possible?
If only substances that cannot form an explosive atmosphere are used – such as water-based systems instead of solvents – no explosion protection measures are needed. This is documented too.
- 4
Reliably prevented?
If tightness, natural ventilation or organisational measures such as removing dust deposits already reliably prevent hazardous explosive atmospheres, a note in the risk assessment is sufficient. If active measures such as technical ventilation or gas detectors are needed for this, or a hazard remains, you need an explosion protection concept and the explosion protection document.
What goes into the explosion protection document?
Section 6 (9) GefStoffV specifies what the document must show in particular:
- that the explosion hazards have been identified and assessed
- the explosion protection concept, i.e. the precautions taken to achieve the aims of explosion protection
- whether and which areas have been classified into zones
- for which areas explosion protection measures under Section 12 and Annex I No. 1 GefStoffV have been taken
- how cooperation with contractors under Section 15 GefStoffV is implemented
- which checks under Section 7 (7) GefStoffV and which inspections under Annex 2 Section 3 of the Ordinance on Industrial Safety and Health are to be carried out
The ordinance does not prescribe a format. The structure of DGUV Information 213-106 “Explosion protection document” (Explosionsschutzdokument) has proven useful: plant section and responsible person, building conditions, process description, substance data with safety parameters such as flash point, explosion limits and ignition temperature, the assessment of where hazardous explosive mixtures can form, and the explosion protection concept with zones and technical and organisational measures.
Hazardous substances management in AMS GoManage safety data sheets centrally, have AI extract the relevant information from all 16 sections with source references, and have outdated data sheets flagged automatically.Zoning: zones 0, 1, 2 and 20, 21, 22
Hazardous areas are classified into zones according to how often and how long a hazardous explosive atmosphere occurs – zones 0 to 2 for gases, vapours and mists, zones 20 to 22 for combustible dusts (Annex I No. 1.7 GefStoffV). The zone determines which equipment may be used there (Annex I No. 1.8):
Zone 0 (gases) / Zone 20 (dusts)
A hazardous explosive atmosphere is present …continuously, for long periods or frequently
Equipment categoryCategory 1
Zone 1 / Zone 21
A hazardous explosive atmosphere is present …occasionally in normal operation
Equipment categoryCategory 1 or 2
Zone 2 / Zone 22
A hazardous explosive atmosphere is present …not normally in normal operation, and if it does occur, only rarely and for a short time
Equipment categoryCategory 1, 2 or 3
Normal operation means operation within the design parameters. If in doubt, the stricter zone applies, and dust layers and deposits must be considered like any other source of explosive atmosphere. Mark the entrances with the warning sign “Warning: explosive atmosphere” (Annex I No. 1.6 (5)); smoking, open flames and access by unauthorised persons must be prohibited there (Annex I No. 1.3 (2)).
Explosion protection concept: protective measures in three stages
The protective measures follow the order of priority in Section 12 (2) GefStoffV; the details are described in TRGS 722 to 725:
- Avoid or limit hazardous explosive mixtures (TRGS 722): substitutes with a high flash point, limiting concentrations, inerting, tight installations, ventilation and extraction, removing dust deposits
- Avoid effective ignition sources (TRGS 723): equipment suited to the zone, earthing and equipotential bonding, protection against electrostatic charging (TRGS 727), banning open flames, permit procedures for hot work
- Limit the effects of an explosion (TRGS 724): explosion-resistant design, explosion venting, explosion suppression and explosion isolation
TRGS 723 lists 13 types of ignition source – including hot surfaces, flames and hot gases, mechanically generated sparks, electrical installations, static electricity, lightning and chemical reactions. For each relevant ignition source, you assess whether it can become effective in normal operation, in foreseeable malfunctions or only in rare malfunctions, and document this in the explosion protection document. Where protective measures depend on measuring, control and regulating devices such as a gas detection system, TRGS 725 applies to their reliability.
Which inspections belong in the explosion protection document?
The explosion protection document specifies which inspections are required. For installations in hazardous areas and the related protective measures, Annex 2 Section 3 of the Ordinance on Industrial Safety and Health (Betriebssicherheitsverordnung, BetrSichV) applies:
Installation before first commissioning and after modifications requiring inspection (No. 4.1)
Intervalbefore (re)commissioning
Who inspectsapproved inspection body (zugelassene Überwachungsstelle, ZÜS) or person qualified to carry out inspections with special qualifications under No. 3.3
Installation periodically for explosion safety (No. 5.1)
Intervalat least every 6 years
Who inspectsZÜS or qualified person under No. 3.3
Equipment, protective systems, safety, control and regulating devices (No. 5.2)
Intervalat least every 3 years
Who inspectsperson qualified to carry out inspections under No. 3.1
Ventilation systems, gas detection systems, inerting systems (No. 5.3)
Intervalannually
Who inspectsperson qualified to carry out inspections under No. 3.1
Function and effectiveness of technical protective measures (Section 7 (7) GefStoffV)
Intervalat least every third year
Who inspectsarranged by the employer, result recorded
For installations requiring a permit under Section 18 (1) Nos. 3 to 7 BetrSichV – such as storage facilities for more than 10,000 litres of flammable liquids with a flash point below 23 °C, filling points and petrol stations – only the ZÜS may carry out the inspections under Nos. 4.1 and 5.1. Instead of the periodic inspections under Nos. 5.2 and 5.3, the employer may set out an equivalent maintenance concept, whose suitability is assessed in the inspection before commissioning (No. 5.4).
When do you need to update the explosion protection document?
Like the risk assessment as a whole, the explosion protection document must be reviewed regularly and updated without delay when significant changes or new information require it (Section 6 (10) GefStoffV). You set the review intervals to suit your company. Typical reasons for an update:
- new or changed substances, quantities, processes or work equipment
- conversions or changes to installations in the hazardous area
- new findings, in particular from accidents and incidents
- inspection results showing that protective measures are not effective or not sufficient
If a review shows no need for changes, record this with the date. A revision sheet with the date, amended section, change and signature makes the current status traceable for inspectors and authorities.
Checklist: explosion protection document
- Flammable substances and activities recorded – including cleaning, maintenance and faults
- Safety parameters taken from safety data sheets or databases
- Substitution with substances that cannot form explosive mixtures checked
- Areas with hazardous explosive atmospheres defined and, where sensible, classified into zones
- Equipment and work equipment selected to suit the zone
- Ignition sources assessed and measures defined
- Entrances marked, smoking ban and ban on unauthorised access in place
- Instruction, operating instructions and permit-to-work system arranged
- Inspections under BetrSichV and Section 7 (7) GefStoffV scheduled with intervals
- Document completed before work starts, review date set
Free templates for this guide
As PDF and Excel, free – to use in your own company.
Frequently asked questions
Is an explosion protection document mandatory?
Yes, if hazardous explosive mixtures can occur during work and this is not already reliably prevented by tightness, natural ventilation or organisational measures. The duty arises from Section 6 (9) GefStoffV and applies regardless of company size. If no hazardous explosive mixtures can form, you record this result in the risk assessment.
Who may prepare an explosion protection document?
The employer is responsible. Only competent persons (fachkundige Personen) may prepare it; if the company lacks the knowledge, the employer must obtain competent advice (Section 6 (11) GefStoffV), for example from the occupational safety specialist or external explosion protection experts. Involve employees and the people responsible for the areas concerned, as they know the processes and faults best.
Do I have to classify hazardous areas into zones?
No, zoning is an option under Annex I No. 1.6 (3) GefStoffV. Without zones, protective measures as for zone 0 or 20 are required unless the risk assessment specifies otherwise (TRGS 720). For activities limited in time and place, rare start-up and shutdown processes and installation and maintenance work, measures are in any case set on the basis of the risk assessment (Annex I No. 1.8 (4)).
How often does the explosion protection document have to be reviewed?
The Hazardous Substances Ordinance does not set a fixed interval: you review it regularly at intervals you define and update it without delay after significant changes (Section 6 (10) GefStoffV). Separately, installations in hazardous areas are inspected for explosion safety at least every six years; the inspector takes the explosion protection document and the zoning into account (Annex 2 Section 3 No. 5.1 BetrSichV).
Terms from the glossary
This guide gives a general overview of German occupational safety law and does not replace legal advice. The regulations in force and the rules of the statutory accident insurance institutions are authoritative.
Organise occupational safety digitally
With the occupational safety software AMS Go you handle risk assessments, safety instructions, inspections and more in one system – mobile and with AI support.
Newsletter
Occupational safety, straight to your inbox
New templates, guides and changes to regulations – free from AMS Go. The newsletter is in German. You can unsubscribe at any time via the link in every email.
More guides
- Hazardous substances
Hazardous substances risk assessment in Germany: duties, TRGS 400 procedure and checklist
8 minRead - Testing duties
Installations subject to monitoring in Germany: inspection duties and approved bodies
7 minRead - Hazardous substances
Storing hazardous substances under TRGS 510: basic rules, storage classes and mixed storage
8 minRead