Inspecting power-operated doors and gates in Germany: duties under ASR A1.7

Roller shutters, sectional doors and automatic doors must be inspected for safe condition before first commissioning, after significant modifications and at recurring intervals. Who may inspect, what the inspection covers, which separate rules apply to hold-open systems on fire doors and how you document the result.

Last updated on 8 min readAMS Go editorial team

Key points at a glance

  • Power-operated doors and gates must be inspected for safe condition in accordance with the manufacturer's specifications before first commissioning, after significant modifications and at recurring intervals; the recurring inspection should take place at least once a year (ASR A1.7 no. 10.2 (1)).
  • Only experts (Sachkundige) who can assess the functioning of the protective devices and verify it with suitable measuring equipment, such as the force curve over time at closing edges, may inspect (ASR A1.7 no. 10.2 (2)).
  • The inspection covers, among other things, mechanics and suspension elements, safety catches, protective devices at closing edges, the control system and the closing forces; the limit values are set out in DIN EN 12453 for gates and DIN EN 16005 for doors.
  • Hold-open systems (Feststellanlagen) on fire doors and fire gates follow their own rules: they are inspected in accordance with the building authority approval or test certificate, for example once a month by the operator and once a year by an expert (ASR A1.7 no. 10.2 (3)).
  • The results of the safety inspection must be recorded and kept at the workplace; an inspection log per gate is customary.

What ASR A1.7 requires

A sectional door easily weighs several hundred kilograms, and its drive moves it regardless of whether someone is in the way. Crushing and shearing points at the closing edges, falling door leaves and being struck are therefore among the typical hazards. The German Workplaces Ordinance (Arbeitsstättenverordnung) requires workplaces to be maintained and safety equipment to be checked regularly; for doors and gates, this is specified in the Technical Rule for Workplaces ASR A1.7 “Türen und Tore” (doors and gates).

Doors and gates are power-operated if the energy for opening or closing the leaves is supplied wholly or partly by powered machinery (ASR A1.7 no. 3.8). This concerns, for example:

  • roller shutters and rolling grilles,
  • sectional doors and up-and-over doors with a drive,
  • sliding gates on halls and at the site entrance,
  • automatic sliding doors and swing doors,
  • revolving doors with a drive,
  • high-speed doors in production and logistics.

The ASR applies to doors and gates in buildings and on company premises to which employees have access in the course of their work. It does not apply to doors and gates of machinery such as lifts, nor to temporary doors and gates on construction sites (ASR A1.7 no. 2).

When inspections are due

The safety inspection follows the manufacturer's specifications. The manufacturer's operating, maintenance and inspection instructions must be available at the workplace (ASR A1.7 no. 10 (1)). This results in the following occasions:

  • Before first commissioning

    WhoExpert

    BasisASR A1.7 no. 10.2 (1) and (2)

  • After significant modifications, for example a new drive, new control system or conversion of the door leaf

    WhoExpert

    BasisASR A1.7 no. 10.2 (1) and (2)

  • Recurring, at least once a year; more often under heavy use

    WhoExpert

    BasisASR A1.7 no. 10.2 (1), DGUV Information 208-022

  • Regular visual and functional check for obvious defects

    WhoOperator, for example instructed employees

    BasisDGUV Information 208-022 no. 10

  • Hold-open systems on fire doors and fire gates: according to approval or test certificate, for example monthly and annually

    Whomonthly operator, annually expert

    BasisASR A1.7 no. 10.2 (3)

Changes of use are also a reason to look more closely: if a rarely used storage door becomes a busy passage or pedestrians are added, you must assess whether the door is still sufficiently safe under the new conditions. The result of the safety inspection must be taken into account; the manufacturer should be involved (ASR A1.7 no. 10 (1)). DGUV Information 208-022 also recommends regular inspection for doors and gates that are not power-operated.

Who may inspect: experts (Sachkundige)

The safety inspection may only be carried out by experts who can assess the functioning of the protective devices and verify it with suitable measuring equipment that, for example, records the force curve over time at closing edges (ASR A1.7 no. 10.2 (2)). A look at the door and a test run are therefore not enough: without a force measuring device it cannot be established whether the closing forces are complied with.

According to DGUV Information 208-022, an expert is someone who, on the basis of their professional training, activity and experience and their knowledge of the relevant occupational safety regulations, workplace rules and generally recognised rules of technology, is able to assess the safe condition of doors and gates. Possible experts are:

  • specialists from the manufacturer or supplier,
  • specialist companies for door and gate technology,
  • your own employees, for example from maintenance, if they have the training, experience and measuring equipment for it.
Inspection register in AMS GoRecord every gate with location, drive and inspection interval, get timely reminders of the annual expert inspection and the checks of hold-open systems, file inspection reports with the gate and track defects as measures.

What is inspected

The inspection relates to the functional safety of the entire door or gate system. It is based on the manufacturer's technical documentation; whether this is complete is itself part of the inspection (ASR A1.7 no. 10.2 (4)). DGUV Information 208-022 names the following inspection points, among others:

  • Documentation

    What mattersTechnical documentation and operating instructions complete, inspection log kept

  • Mechanics and fastenings

    What mattersStability of components, wear, corrosion, damage, free movement of moving parts, guiding and load-bearing parts

  • Suspension elements and counterbalance

    What mattersSprings for breakage and correct tension, ropes for broken wires and kinks, chains, shafts, fastening of counterweights

  • Safety catch

    What mattersInspection according to the manufacturer's instructions; type-examined safety catches do not need a function test

  • Protective devices

    What mattersSafety edges, light barriers and other devices at the closing edges trigger and stop or reverse the movement

  • Closing and opening forces

    What mattersMeasurement of the static and dynamic forces between main, secondary and opposing closing edges; limit values under DIN EN 12453 and DIN EN 16005

  • Drive and control system

    What mattersFastening, bearings, noise and tightness of the drive, limit switching, control devices, mains isolating device, emergency stop where fitted

  • Sequence of movement

    What mattersInteraction of all components when opening, closing and stopping

Doors and gates may only be repaired by persons familiar with the work in question. Before maintenance work, the leaves are secured against unintended movement and the drive is switched off and secured against being switched on by mistake or without authorisation; the test run is excepted (ASR A1.7 no. 10.1).

Closing forces and safety devices

Power-operated doors and gates must have effective protection against mechanical hazards up to a height of 2.50 metres above the floor or another permanent access level. ASR A1.7 permits individual measures or a combination for this purpose (no. 6 (1)):

  • maintaining safety distances so that no crushing or shearing points arise,
  • guards at the closing edges such as housings, covers or cladding,
  • suitable shaping of leaf surfaces and protruding parts,
  • operation with a hold-to-run control (Totmannsteuerung),
  • limiting the forces the leaf generates when it meets a person or an object,
  • tripping protective devices, i.e. pressure-sensitive ones such as safety edges or non-contact ones such as light barriers.

The ASR itself gives no figures for force limitation; the product standards are decisive. DGUV Information 208-022 reproduces the values as an extract: for gates under DIN EN 12453, the dynamic force for vertically closing leaves and for horizontally closing leaves up to an opening width of 500 millimetres may not exceed 400 newtons and may act for no more than 0.75 seconds; after that the static force must fall to no more than 150 newtons. For doors, DIN EN 16005 contains comparable values graded by opening width. Only measurement shows whether your gate complies.

With a hold-to-run control, the other safeguards can be dispensed with if the movement stops immediately on release, the danger zone is fully visible from the operating position, unauthorised persons cannot operate the control device and the closing speed at the main closing edge does not exceed 0.5 metres per second (ASR A1.7 no. 8.1).

Hold-open systems on fire doors and fire gates

Hold-open systems keep fire and smoke control doors open in everyday use and release them in the event of fire so that they close automatically. A separate inspection regime applies to them: fire doors and fire gates must be inspected regularly in accordance with the general building authority approval or the test certificate so that they close properly in an emergency. As an example, ASR A1.7 names inspection of hold-open systems once a month by the operator and once a year by the expert (no. 10.2 (3)). If there is no building authority approval because the product was placed on the market with CE marking, the inspection follows the manufacturer's installation and maintenance instructions (DGUV Information 208-022).

  • The intervals and inspection steps in the approval, test certificate or manufacturer's instructions for the specific system are decisive. Read them before you set intervals.
  • The check by the operator can be carried out by instructed employees; the annual inspection belongs in the hands of an expert for hold-open systems.
  • Every inspection is documented with date, result and inspector.
  • The closing area stays clear: no pallets, wedges or cables that prevent closing.
  • Defects in fire barriers are reported and remedied immediately because they render the fire compartment ineffective.

Power-operated gates that are also fire barriers must meet both sets of requirements: they may only be used if they close automatically without endangering employees when the power supply fails. If a protective device at the closing edge interrupts the movement, the closing process initiated in the event of fire must continue automatically once the device is released (ASR A1.7 no. 8.3).

Inspection log, defects and checklist

The results of the safety inspection must be recorded and kept at the workplace (ASR A1.7 no. 10.2 (1)). An inspection log (Prüfbuch) per gate, often supplied by the manufacturer, is customary; the record can also be kept digitally. It contains the gate with location and type, date and scope of the inspection, the closing forces measured, defects found with a deadline for rectification, the result and the name of the expert. An inspection sticker on the gate does not replace the record. For your own documentation you can use the template “Power-operated door and gate inspection report”.

  • All power-operated doors and gates recorded with location, manufacturer, year of manufacture and drive
  • Manufacturer's operating, maintenance and inspection instructions available at the workplace
  • Inspection before first commissioning and after significant modifications documented
  • Recurring inspection by an expert scheduled at least once a year
  • Closing forces measured and readings recorded in the inspection report
  • Safety catch, suspension elements and protective devices expressly assessed in the inspection report
  • Defects tracked with responsible person and deadline; gate shut down and secured in the event of dangerous defects
  • Hold-open systems inspected and documented according to approval or manufacturer's instructions
  • Employees instructed: do not pass under a moving gate, do not bypass protective devices, report anything unusual

Frequently asked questions

How often do power-operated gates have to be inspected?

Before first commissioning, after significant modifications and at recurring intervals. Under ASR A1.7 no. 10.2, the recurring inspection should take place at least once a year. DGUV Information 208-022 understands this to mean an inspection every twelve months under normal use; with intensive use or harsh ambient conditions, shorter intervals may be necessary. The manufacturer's specifications are also decisive.

Who may inspect power-operated gates?

Only experts (Sachkundige) who can assess the functioning of the protective devices and verify it with suitable measuring equipment (ASR A1.7 no. 10.2 (2)). These can be specialists from the manufacturer, from a specialist gate company or suitably trained employees of your own. What counts is training, experience, knowledge of the rules and a measuring device for the closing forces.

Does the inspection duty also apply to manually operated gates?

The safety inspection under ASR A1.7 no. 10.2 concerns power-operated doors and gates. Manually operated gates must nevertheless be maintained and be safe, for example against leaves falling or coming out of their guides. DGUV Information 208-022 therefore recommends regular inspection for doors and gates that are not power-operated as well.

How often are hold-open systems on fire doors inspected?

That depends on the building authority approval, the test certificate or the manufacturer's instructions for the system. ASR A1.7 names as an example inspection once a month by the operator and once a year by an expert (no. 10.2 (3)). The inspections are documented.

Is an inspection log for gates mandatory?

What is required is that the results of the safety inspection are recorded and kept at the workplace (ASR A1.7 no. 10.2 (1)). The ASR does not prescribe a particular form. An inspection log per gate has proved its worth because it brings manufacturer's information, inspection reports and repairs together in one place; digital documentation serves the same purpose.

This guide gives a general overview of German occupational safety law and does not replace legal advice. The regulations in force and the rules of the statutory accident insurance institutions are authoritative.

Organise occupational safety digitally

With the occupational safety software AMS Go you handle risk assessments, safety instructions, inspections and more in one system – mobile and with AI support.

Newsletter

Occupational safety, straight to your inbox

New templates, guides and changes to regulations – free from AMS Go. The newsletter is in German. You can unsubscribe at any time via the link in every email.

Privacy information

Contact

Get in touch

Book an appointment with us – or send us a message.

Kim Marius GräfeFrank MezlerLukas KleinBenjamin Kostrzewa

Personal and direct – with our founding team. Meet the founding team