Inspection intervals table: German inspection deadlines for work equipment and installations
How often do electrical equipment, ladders, forklifts, cranes, doors, fire extinguishers or lifts have to be inspected in Germany? The table shows maximum intervals and guide values, who inspects and where the rule comes from – grouped for quick reference.
Last updated on 9 min readAMS Go editorial team
Key points at a glance
- The employer sets the type, scope and intervals of inspections in the risk assessment; the intervals must ensure safe use until the next inspection and must not exceed the maximum intervals in the annexes (Section 3(6) of the Industrial Safety and Health Ordinance, BetrSichV).
- Binding maximum intervals exist mainly for installations subject to monitoring and for cranes (Annexes 2 and 3 BetrSichV) and in accident prevention regulations, for example at least annually for forklifts and vehicles (DGUV Regulations 68 and 70).
- For many other items, DGUV regulations and rules, technical rules and standards give guide values – such as 6 months for portable electrical equipment or 12 months for racking; you must justify any deviation.
- Inspections are carried out by qualified persons (Section 2(6) BetrSichV), and installations subject to monitoring generally by an approved inspection body (ZÜS); the result is recorded (Sections 14(7) and 17 BetrSichV).
How to read the inspection intervals table
This page is the quick-reference overview. How intervals are set, inspectors selected and inspections documented is explained in detail in the guide on inspection intervals for work equipment. German law has no single table of fixed intervals for all work equipment: the employer determines the type and scope of the required inspections and the intervals for recurring inspections in the risk assessment. The intervals must be set so that the equipment can be used safely until the next inspection and must not exceed the maximum intervals in the annexes of the Industrial Safety and Health Ordinance (Section 3(6) BetrSichV). The employer also defines the requirements the inspecting persons must meet.
- Maximum interval or “at least annually”: a binding requirement from an ordinance or accident prevention regulation, for example Annexes 2 and 3 BetrSichV or DGUV Regulations 68 and 70. Shorter is always allowed, longer is not.
- Guide value (Richtwert): orientation from implementation notes, DGUV rules and information, technical rules or standards. It applies to normal conditions; if you deviate, justify it in the risk assessment.
- In practice: the usual interval where no regulation states a figure – ladders, for example. It must still match how hard the equipment is used.
- Qualified person (zur Prüfung befähigte Person): someone with the knowledge required for inspections through vocational training, professional experience and recent professional activity (Section 2(6) BetrSichV, TRBS 1203). Some regulations speak of a competent person (Sachkundiger or Fachkundiger).
- ZÜS (zugelassene Überwachungsstelle): an approved inspection body such as TÜV or DEKRA. It inspects installations subject to monitoring unless Annex 2 BetrSichV allows a qualified person (Sections 15 and 16 BetrSichV).
For installations subject to monitoring under Annex 2 Parts 2 to 4 and for the equipment listed in Annex 3 BetrSichV, such as cranes and LPG installations, due dates are stated as month and year. A recurring inspection there counts as on time if it takes place no later than two months after the due date (Section 14(5) BetrSichV). This tolerance does not apply to any other work equipment.
Electrical installations and equipment
The guide values come from the implementation notes to Section 5 of DGUV Regulation 3 (Tables 1A to 1C); for companies insured with a public-sector accident fund, the identical DGUV Regulation 4 applies. Details on the error rate and the inspection procedure are in the guide on DGUV Regulation 3.
Fixed electrical installations and equipment
IntervalGuide value 4 years
Inspected byQualified electrician (Elektrofachkraft)
Legal basisDGUV Regulation 3, Table 1A
Installations and fixed equipment in special locations and facilities (DIN VDE 0100 group 700)
IntervalGuide value 1 year
Inspected byQualified electrician
Legal basisDGUV Regulation 3, Table 1A
Protective measures with residual current devices in non-stationary installations, for example on construction sites
IntervalGuide value 1 month
Inspected byQualified electrician or electrotechnically instructed person with suitable measuring and test equipment
Legal basisDGUV Regulation 3, Table 1A
Residual current circuit breakers: pressing the test button
Interval6 months in stationary installations, every working day in non-stationary installations
Inspected byUser
Legal basisDGUV Regulation 3, Table 1A
Portable equipment, extension leads and appliance connection leads
IntervalGuide value 6 months, 3 months on construction sites; with an error rate below 2 percent, may be extended to a maximum of 1 year (construction sites, production facilities, workshops) or 2 years (offices)
Inspected byQualified electrician or electrotechnically instructed person under the direction and supervision of a qualified electrician, with suitable measuring and test equipment
Legal basisDGUV Regulation 3, Table 1B
Insulating protective clothing
IntervalBefore each use for obvious defects; test against limit values every 12 months, insulating gloves every 6 months
Inspected byUser; qualified electrician
Legal basisDGUV Regulation 3, Table 1C
Ladders, racking, scaffolds and fall protection equipment
Ladders and step stools
IntervalVisual check before each use; regular inspection based on the risk assessment, in practice usually every 12 months, more often under harsh use
Inspected byUser; qualified person
Legal basisSection 14 BetrSichV, DGUV Information 208-016
Racking and storage equipment
IntervalInspection at least every 12 months; visual checks in between based on the risk assessment, often weekly
Inspected byQualified person with knowledge of racking systems; person responsible for storage equipment
Legal basisSection 14 BetrSichV, DIN EN 15635, DGUV Information 208-061
Scaffolds
IntervalAfter each erection or modification before use; visual inspection before use, at least every working day according to DGUV Information 201-011; after exceptional events such as storms
Inspected byQualified person; competent person of the scaffold user
Legal basisSections 4 and 14 BetrSichV, TRBS 2121 Part 1
Fall protection equipment, such as full body harnesses and lanyards
IntervalVisual check before each use; as needed, at least every 12 months; after a fall before further use
Inspected byUser; competent person
Legal basisDGUV Rule 112-198, No. 10.3
Forklifts, cranes, aerial work platforms and vehicles
For industrial trucks and vehicles, the accident prevention regulations set a minimum interval; for cranes, the BetrSichV itself does. In practice these inspections are often called the “UVV inspection” (UVV-Prüfung).
Industrial trucks such as forklifts, including attachments
IntervalAt most 1 year; safety devices for narrow-aisle operation checked daily for function unless a failure is indicated automatically
Inspected byCompetent person (Sachkundiger)
Legal basisSection 37 DGUV Regulation 68
Power-driven cranes, such as overhead travelling, gantry and slewing jib cranes
IntervalAt least annually
Inspected byQualified person
Legal basisBetrSichV Annex 3 Part 1, DGUV Regulation 52
Tower cranes, mobile cranes, large truck-mounted loader cranes and other cranes listed in Table 1
IntervalAdditionally at least every 4 years of operation; mobile cranes and large truck-mounted loader cranes annually from the 13th year of operation, tower cranes in the 14th and 16th year and annually thereafter
Inspected byInspection expert (Prüfsachverständiger)
Legal basisBetrSichV Annex 3 Part 1 Table 1
Load handling and lifting accessories such as spreader beams, chains, wire ropes and lifting slings
IntervalAt most 1 year; round steel chains additionally checked for cracks at most every 3 years
Inspected byQualified person
Legal basisDGUV Rule 109-017
Mobile elevating work platforms and vehicle lifts
IntervalVisual and function check after set-up and every working day; recurring inspection at most annually
Inspected byOperator; competent or qualified person
Legal basisSection 14 BetrSichV, DGUV Principle 308-002
Vehicles such as cars, vans, trucks and trailers
IntervalAs needed, at least annually – independent of the statutory roadworthiness test (Hauptuntersuchung)
Inspected byCompetent person
Legal basisSection 57 DGUV Regulation 70
Doors, gates and fire protection equipment
Power-operated doors and gates
IntervalBefore first use, after significant modifications and recurring; the ASR recommends at least once a year
Inspected byCompetent person
Legal basisTechnical Rule for Workplaces ASR A1.7, No. 10.2
Hold-open devices on fire doors and gates
IntervalAccording to approval or test certificate; as an example the ASR names monthly by the operator and annually by a competent person
Inspected byOperator; competent person
Legal basisASR A1.7, No. 10.2
Fire extinguishers
IntervalMaintenance every 2 years; the employer may adopt longer manufacturer intervals, shorter ones must be followed; shorter under heavy use
Inspected byCompetent person, usually a specialist under DIN 14406-4
Legal basisASR A2.2, No. 7.4.2
Fire detection and firefighting equipment such as wall hydrants, and safety lighting
IntervalAt regular intervals according to the manufacturer; the Workplaces Ordinance (ArbStättV) and ASR A2.2 set no fixed interval
Inspected byCompetent person or specialist company
Legal basisSection 4(3) ArbStättV, ASR A2.2 No. 7.4.1
In special buildings (Sonderbauten), additional inspection duties for safety installations under the building regulations of the federal states may apply. The relevant intervals follow from the building permit and the respective state ordinance.
Lifts, pressure equipment, Ex areas and LPG installations
For installations subject to monitoring (Section 2(13) BetrSichV) and for LPG installations, the BetrSichV sets maximum intervals. Whether a qualified person or the approved body inspects a pressure equipment part depends on pressure, volume and fluid (Annex 2 Part 4 No. 6, Tables 2 to 11).
Lift installations: main inspection
IntervalAt most 2 years
Inspected byApproved body (ZÜS)
Legal basisBetrSichV Annex 2 Part 2 No. 4.1
Lift installations: intermediate inspection
IntervalHalfway between two main inspections
Inspected byApproved body (ZÜS)
Legal basisBetrSichV Annex 2 Part 2 No. 4.3
Pressure vessels inspected by the approved body
IntervalExternal inspection 2 years (with exceptions), internal inspection 5 years, strength test 10 years
Inspected byApproved body (ZÜS)
Legal basisBetrSichV Annex 2 Part 4 No. 5.8
Pressure equipment parts that a qualified person may inspect
IntervalAt most 10 years; strength test up to 15 years with evidence
Inspected byQualified person
Legal basisBetrSichV Annex 2 Part 4 No. 5.9
Installations in explosion hazard areas: inspection for explosion safety
IntervalAt least every 6 years
Inspected byApproved body or qualified person under No. 3.3
Legal basisBetrSichV Annex 2 Part 3 No. 5.1
Ex equipment, protective systems and safety, control and regulating devices
IntervalAt most 3 years
Inspected byQualified person under No. 3.1
Legal basisBetrSichV Annex 2 Part 3 No. 5.2
Ventilation systems, gas warning and inerting devices in Ex areas
IntervalAnnually
Inspected byQualified person under No. 3.1
Legal basisBetrSichV Annex 2 Part 3 No. 5.3
LPG installations
IntervalMobile at least every 2 years, fixed at least every 4 years, with consumer appliances in rooms below ground level at least annually
Inspected byQualified person
Legal basisBetrSichV Annex 3 Part 2 No. 4.1
Extraction systems, respiratory protection, AEDs and first aid supplies
Technical protective measures for hazardous substances, such as extraction and ventilation systems
IntervalRegularly, at least every third year for function and effectiveness; record the result
Inspected byCompetent person commissioned by the employer
Legal basisSection 7(7) Hazardous Substances Ordinance (GefStoffV)
Respiratory protective equipment
IntervalClean, disinfect and check after each use; stored equipment according to the maintenance and inspection intervals of the rule and the manufacturer's instructions
Inspected byPerson qualified according to the manufacturer and DGUV Rule 112-190
Legal basisDGUV Rule 112-190
Automated external defibrillators (AEDs)
IntervalSafety check at the latest every 2 years; not required for self-testing AEDs intended for laypersons if the operator carries out regular visual checks; electrodes and battery according to the manufacturer
Inspected byPerson qualified for the safety check; operator
Legal basisSection 12 Medical Devices Operator Ordinance (MPBetreibV)
First aid kits and other first aid supplies
IntervalRegularly for completeness and usability – there is no fixed interval; in practice after each use and about quarterly
Inspected byAppointed person, for example a first aider
Legal basisSection 4(5) ArbStättV
Checklist: organising inspection intervals in your company
The table only helps if the intervals are actually tracked in the company. These points belong in every inspection organisation:
- All work equipment and installations subject to inspection recorded per site, with unique identification
- Type, scope and interval of inspection defined and justified for each item in the risk assessment
- Maximum intervals from Annexes 2 and 3 BetrSichV and from the accident prevention regulations complied with
- Inspector defined for each inspection: qualified person, competent person, qualified electrician, inspection expert or approved body
- Due dates planned by month and year and external inspectors booked in good time
- Checks before use and daily inspections covered in operating instructions and safety training
- Inspection results recorded – at least until the next inspection, for cranes, LPG installations and installations subject to monitoring for their entire service life
- Defects found tracked with a responsible person and deadline
- Intervals reviewed regularly based on inspection results, for example via the error rate for electrical equipment
Free templates for this guide
As PDF and Excel, free – to use in your own company.
Frequently asked questions
Is there a statutory table of all inspection intervals in Germany?
No. The Industrial Safety and Health Ordinance obliges employers to set the type, scope and intervals of inspections themselves in the risk assessment (Section 3(6) BetrSichV). Fixed maximum intervals are laid down in legislation only for certain equipment – for example for lifts, pressure equipment and Ex installations in Annex 2, for cranes and LPG installations in Annex 3 BetrSichV and for forklifts and vehicles in DGUV Regulations 68 and 70. For everything else, rules, standards and manufacturer instructions provide guide values.
May I extend guide values such as the 6 months for electrical equipment?
Yes, if you can justify it. For portable electrical equipment, DGUV Regulation 3 allows an extension if the error rate in inspections is below 2 percent – to a maximum of 1 year on construction sites, in production facilities and workshops and 2 years in offices. You must not, however, exceed binding maximum intervals from ordinances and accident prevention regulations.
Who may carry out the inspections?
As a rule, a qualified person who has the necessary knowledge through vocational training, professional experience and recent professional activity (Section 2(6) BetrSichV). Electrical inspections are reserved for qualified electricians; portable equipment may also be inspected by electrotechnically instructed persons under their direction. Installations subject to monitoring are generally inspected by an approved body (ZÜS), certain cranes additionally by an inspection expert.
What applies if an inspection interval has been exceeded?
Equipment subject to inspection may only be used if the inspections have been carried out and documented (Section 4(4) BetrSichV). Only for installations subject to monitoring and equipment under Annex 3, such as cranes, does a recurring inspection still count as on time if it takes place no later than two months after the due date (Section 14(5) BetrSichV). If the inspection is overdue, take the equipment out of service until it has been inspected.
How long do I have to keep inspection records?
At least until the next inspection (Section 14(7) BetrSichV). For cranes and LPG installations, the entire service life applies (Annex 3 BetrSichV), as it does for inspection records and certificates of installations subject to monitoring, which are kept at the operating site (Section 17 BetrSichV). If you want to justify intervals using the error rate, keep records longer anyway.
This guide gives a general overview of German occupational safety law and does not replace legal advice. The regulations in force and the rules of the statutory accident insurance institutions are authoritative.
Organise occupational safety digitally
With the occupational safety software AMS Go you handle risk assessments, safety instructions, inspections and more in one system – mobile and with AI support.
Newsletter
Occupational safety, straight to your inbox
New templates, guides and changes to regulations – free from AMS Go. The newsletter is in German. You can unsubscribe at any time via the link in every email.
More guides
- Inspections
Inspection intervals for work equipment in Germany: overview, duties and records
8 minRead - Testing duties
DGUV Regulation 3: testing electrical equipment – intervals, process and records
8 minRead - Testing duties
UVV inspections in Germany: what must be inspected, how often and by whom
8 minRead - Testing duties
Installations subject to monitoring in Germany: inspection duties and approved bodies
7 minRead - Testing duties
Qualified person for inspections under TRBS 1203 in Germany: requirements, duties and appointment
6 minRead