Storing and charging lithium batteries safely at work in Germany
Cordless tools, e-bikes and power banks are part of everyday working life – and a fire load that can ignite by itself. Which rules apply although there is no dedicated statute, how you set up storage and charging areas, what happens to damaged batteries and how to react correctly in the event of fire.
Last updated on 9 min readAMS Go editorial team
Key points at a glance
- There is no dedicated public-law regulation in Germany for storing and staging lithium batteries. What counts are the risk assessment under Section 5 of the Occupational Safety and Health Act (ArbSchG), the manufacturer's specifications and recognised recommendations such as DGUV Information 205-041 and the insurers' publication VdS 3103.
- When used as intended, lithium-ion batteries are considered safe. Fire hazards arise mainly from mechanical damage, heat, overcharging, deep discharge and short circuits.
- Charging is done with the manufacturer's charger on a non-combustible surface, with no fire loads nearby and preferably under supervision – alternatively monitored by fire detectors connected to a fire alarm system or in a room separated for fire protection purposes (DGUV Information 205-041).
- Damaged or defective batteries are no longer used, are taken to a safe place immediately and are disposed of.
- Extinguishing and cooling is done with water; the DGUV rates attempts by employees to extinguish with a fire extinguisher as extremely critical because of the risk to themselves.
Legal situation: no dedicated statute, but clear duties
There is no “lithium battery ordinance”. In their publication VdS 3103, the insurers state expressly that there are so far no public-law regulations for storing and staging lithium batteries. That does not mean you are free to do as you like: the general duties of occupational safety and fire protection also apply to batteries, and what counts as an appropriate protective measure is judged by inspectors, courts and insurers against the published recommendations.
- Risk assessment: the hazards arising from batteries and from equipment containing batteries must be assessed under Section 5 of the Occupational Safety and Health Act; protective measures are defined according to the STOP principle.
- Fire protection in the workplace: where larger quantities of lithium-ion batteries are regularly staged, prepared for dispatch, repaired or tested in work areas, DGUV Information 205-041 classifies these areas as workplaces with increased fire risk within the meaning of the workplace rule ASR A2.2. Additional measures beyond the basic provision of fire extinguishing equipment are then necessary.
- DGUV Information 205-041 “Brandschutz beim Umgang mit Lithium-Ionen-Batterien” (fire protection when handling lithium-ion batteries, February 2024 edition): guidance from the accident insurance institutions on handling, charging, storage, transport and firefighting.
- VdS 3103 “Lithium-Batterien”: a loss prevention publication of the German insurers. It is non-binding but is used by property insurers as a benchmark.
- Dangerous goods law: lithium batteries are always dangerous goods when transported.
- Battery law: take-back and disposal of waste batteries are governed by the EU Batteries Regulation (EU) 2023/1542 and the German Batterierecht-Durchführungsgesetz (BattDG), which replaced the Batteries Act (BattG) in 2025.
Why lithium batteries burn
Lithium-ion cells store a lot of energy in a small space. If a cell is damaged or operated outside its specification, the stored energy can be released uncontrollably as heat. This thermal runaway spreads to neighbouring cells; the fire spreads quickly, releases a lot of smoke and can reignite. Typical triggers are:
- mechanical impact such as falls, blows, crushing or shaking during transport,
- thermal impact such as fire, high temperatures and direct sunlight,
- overcharging, for example by an unsuitable charger,
- deep discharge after long storage,
- external short circuit when conductive objects such as screws or keys bridge the contacts,
- tampering with, opening or attempting to repair the battery.
Besides the fire itself, DGUV Information 205-041 names further hazards: hot housing parts being thrown off, leaking electrolyte and harmful fire smoke, some of which contains carcinogenic substances such as nickel and cobalt compounds, electrical hazards and – if escaping gases collect in a poorly ventilated room – the formation of an explosive atmosphere.
Storing batteries: quantities, distances, conditions
The publication VdS 3103 divides lithium batteries into three categories by power and links graded recommendations for storage and production areas to them. It does not apply to the collection of used batteries or to recycling.
Low power
Lithium-ion batteryup to 100 Wh per battery
ExamplesBatteries for computers, multimedia, small appliances and small tools
Recommendation under VdS 3103General safety rules; for larger contiguous quantities (more than 7 m³ or more than six Euro pallets) as for medium power
Medium power
Lithium-ion batterymore than 100 Wh per battery and up to 12 kg gross
ExamplesBatteries for pedelecs, e-bikes, e-scooters and larger garden equipment
Recommendation under VdS 3103Separate spatially (at least 5 m) or structurally with fire-resistant construction, avoid mixed storage with products that accelerate fire, fire alarm system connected to a permanently staffed location; with more than 60 m² occupied area or more than 3 m storage height as for high power
High power
Lithium-ion batterymore than 100 Wh per battery and/or more than 12 kg gross
ExamplesBatteries for electric vehicles and large off-grid equipment
Recommendation under VdS 3103Agree protective measures with the property insurer case by case, for example quantity limits, fire-resistant separated areas or 5 m distance, automatic extinguishing systems
Regardless of the category, basic rules apply that VdS 3103 and DGUV Information 205-041 both name:
- Comply with the specifications of the manufacturer and the product data sheets.
- Store on a non-combustible surface and keep a distance from fire loads. In areas without an automatic extinguishing system, VdS 3103 recommends structural or spatial separation of at least 2.5 m from other combustible materials; the DGUV recommends a clear strip of 2.5 m inside buildings or an area separated for fire protection purposes.
- Protect terminals against short circuits, for example with terminal caps or by taping them.
- Protect against mechanical damage and do not expose permanently to high temperatures, heat sources or direct sun.
- Store cool, frost-free and dry. According to the DGUV Information, lithium-ion batteries age least at a state of charge between 40 and 60 per cent; during long storage, check the state of charge and recharge to avoid deep discharge.
- Do not store together with hazardous substances and combustible materials: according to the DGUV Information, lithium-ion batteries are regarded as a possible ignition source within the meaning of the Technical Rule TRGS 510.
- Store only cells and batteries for which proof of testing under UN 38.3 is available.
- Stage only the daily requirement at workstations and keep suitable fire extinguishing equipment nearby.
Charging batteries: setting up charging areas
The fire hazard is increased during charging. Where charging takes place should therefore not be left to chance: DGUV Information 205-041 counts defining the place where charging takes place among the organisational protective measures. Unless the manufacturer specifies otherwise, the following guidance applies:
- Use only the charger recommended by the manufacturer; the charging curve is matched to the battery.
- Charge on a non-combustible surface in a dry and dust-free area; there must be no fire loads nearby.
- Charge under supervision wherever possible. Alternatively, monitoring by fire detectors connected to a fire alarm system or charging in a room separated for fire protection purposes is possible.
- Do not charge at ambient temperatures below 0 °C; bring cold batteries to room temperature before charging.
- Protect chargers from moisture and dust, do not cover them during charging and check them regularly for proper condition.
- Do not deep-discharge or overcharge batteries.
- Charge only undamaged batteries.
Chargers are electrical work equipment and belong in the recurring inspection of electrical equipment. Damaged chargers and charging cables are taken out of service immediately, just like damaged batteries.
Damaged batteries and what to do in the event of fire
- 1
Stop using and do not charge
Damaged or tampered batteries are taken out of service immediately. This also applies after a fall, even if little can be seen from the outside: in case of doubt, the manufacturer or a technically competent person assesses the condition.
- 2
Take to a safe place
The safe place (quarantine area) is a storage location where a fire cannot spread and cannot damage the surroundings, for example outdoors at a distance from buildings and combustible materials or in an area separated for fire protection purposes. Define it before you need it.
- 3
Store separately and secured
According to DGUV Information 205-041, damaged batteries are stored in acid-resistant containment separately from combustible materials; the terminals are insulated. Collection containers do not belong in escape routes.
- 4
Dispose of properly without delay
Disposal follows the manufacturer's instructions. Special dangerous goods rules apply to the transport of defective batteries; arrange collection with the manufacturer, the take-back scheme or a specialist waste management company.
If a battery is burning, DGUV Information 205-041 states that only extinguishing agents with a high cooling effect may be used, i.e. water, possibly with additives. The aim is prolonged cooling so that further cells do not go into thermal runaway. Metal fire powder and carbon dioxide are not suitable for extinguishing burning lithium-ion batteries, even if some manufacturers' information says otherwise. For employees' behaviour this means:
- Warn people, leave the area, call the fire brigade on 112 and state that lithium batteries are burning.
- Do not inhale smoke; close doors if this is possible without danger.
- Attempt to extinguish only without endangering yourself: the DGUV rates extinguishing with a fire extinguisher as extremely critical with regard to the protection of employees, including fire safety assistants. In its assessment this also applies to specially advertised lithium-ion fire extinguishers; there is so far no test principle for their extinguishing effectiveness.
- Expect reignition: an extinguished battery can flare up again and belongs in the safe place under observation.
- After the fire, the area is regarded as contaminated (TRGS 524); remediation belongs in the hands of a specialist company.
Transport and disposal
Lithium batteries are always dangerous goods within the meaning of transport law. ADR applies on the road, RID to rail, the IMDG Code to sea freight and the ICAO TI or IATA DGR to air freight. Dangerous goods law applies to commercial and private consignors alike. The most important UN numbers:
UN 3480
DesignationLithium-ion batteries
Examplesindividual batteries, power packs
UN 3481
DesignationLithium-ion batteries contained in equipment or packed with equipment
Exampleslaptop, cordless screwdriver, e-bike
UN 3090
DesignationLithium metal batteries
Examplesbutton cells
UN 3091
DesignationLithium metal batteries contained in equipment or packed with equipment
Examplesdevices with a built-in lithium metal battery
- Transport should only take place if the test summary under UN 38.3 is available; manufacturers and distributors must provide it.
- Relaxed conditions exist for smaller batteries up to 100 Wh that are not defective or damaged. Packages usually bear hazard label no. 9A or the mark under special provision 188.
- Secure contacts against short circuits and protect batteries against slipping and impact – including in the service van and the car boot.
- Stricter requirements apply to damaged or defective batteries; they may only be carried in containers approved and tested for the purpose.
- Waste batteries do not belong in residual waste. Manufacturers and retailers take them back. Tape the terminals before handing them in.
The details of dangerous goods law change regularly and depend on battery type, energy content, condition and mode of transport. Anyone who ships batteries or carries them in larger numbers should check the current packing instructions and special provisions or involve a dangerous goods specialist.
Checklist: lithium batteries at work
- Inventory recorded: which batteries and battery-powered devices exist, with what energy, where they are stored and charged
- Risk assessment prepared for use, charging, storage and transport
- Charging areas defined: non-combustible surface, no fire loads, supervision or fire detectors
- Only original chargers or chargers approved by the manufacturer in use, chargers included in electrical inspections
- Storage areas at a distance from combustible materials or separated for fire protection purposes, quantities limited
- Safe place for damaged batteries defined, suitable container available
- Disposal route and transport of defective batteries clarified with manufacturer or waste contractor
- Rules for e-bikes and private batteries set and communicated
- Employees instructed on the basis of operating instructions: warning signs, charging, behaviour in the event of fire
- Property insurer informed, requirements from the insurance contract implemented
Frequently asked questions
Is there a regulation for storing lithium batteries in Germany?
There is so far no dedicated public-law regulation for storage and staging; the publication VdS 3103 also states this. The general duties apply: risk assessment under Section 5 ArbSchG, fire protection under workplace law and building law, and the manufacturer's specifications. DGUV Information 205-041 and VdS 3103 serve as benchmarks. Dangerous goods law applies to transport.
May batteries be charged overnight without supervision?
DGUV Information 205-041 recommends charging under supervision wherever possible. As alternatives it names monitoring by fire detectors connected to a fire alarm system or charging in a room separated for fire protection purposes. Anyone who charges overnight without such precautions deviates from this recommendation. Also check the requirements of the manufacturer and of your property insurer.
Which fire extinguisher is suitable for lithium batteries?
According to DGUV Information 205-041, only extinguishing agents with a high cooling effect may be used, i.e. water, possibly with additives. Metal fire powder and carbon dioxide are unsuitable. However, the DGUV points out that attempts by employees to extinguish with fire extinguishers are extremely critical because of the risk to themselves and that there is no test principle for the extinguishing effectiveness of specially advertised lithium extinguishers. Raising the alarm and evacuating take priority.
Do I need a safety cabinet for batteries?
There is no obligation to have one. What is recommended is storage at a distance from combustible materials or in an area separated for fire protection purposes; this can be a cabinet or container. DGUV Information 205-041 points out that so far there is only a test principle and no standard for storage cabinets. Which solution fits follows from the risk assessment and coordination with the insurer.
What do I do with a swollen or dropped battery?
Do not continue to use it and do not charge it. Take the battery to the designated safe place, store it separately from combustible materials in a suitable container and insulate the terminals. It is then disposed of properly in accordance with the manufacturer's instructions. Special dangerous goods rules apply to the transport of defective batteries.
This guide gives a general overview of German occupational safety law and does not replace legal advice. The regulations in force and the rules of the statutory accident insurance institutions are authoritative.
Organise occupational safety digitally
With the occupational safety software AMS Go you handle risk assessments, safety instructions, inspections and more in one system – mobile and with AI support.
Newsletter
Occupational safety, straight to your inbox
New templates, guides and changes to regulations – free from AMS Go. The newsletter is in German. You can unsubscribe at any time via the link in every email.
More guides
- Fire safety
Fire extinguishers at work: calculating the number, inspection and mounting
8 minRead - Hazardous substances
Storing hazardous substances under TRGS 510: basic rules, storage classes and mixed storage
8 minRead - Fire safety
Fire safety rules in Germany: parts A, B and C under DIN 14096
7 minRead - Fire safety
Fire safety officer in Germany: when it is mandatory, duties and training
7 minRead - First aid & fire safety
First aiders and fire wardens in Germany: how many does a company need?
8 minRead